Product classification
Product features:
Product Category: Chiller
Key words: box type cold water machine
<div> <ul> <li>International top brand semi-closed 5:6 asymmetric twin-screw compressor, with international famous brand refrigeration valve.</li> <li>The 4-stage energy adjustment mode can realize the maximum control of 25%-50%-75%-100 four-stage automatic control.</li> <li>High efficiency external thread copper tube shell and tube heat exchanger. Ensure that the chiller is not affected by the ambient temperature.</li> <li>International famous brand "Schneider" Electric, imported programmable controller and LCD touch screen, Chinese and English man-machine interface.</li> <li>Multiple protection devices. Ensure the stable operation of the unit throughout the year.</li> <li>Ultra-wide freezing water temperature variable range to meet different user requirements.</li> <li>The use of ethylene glycol as a cold carrier can make the frozen water temperature as low as -30 degrees Celsius.</li> </ul> </div>
Water-cooled screw chiller parameter table (7 ℃ water outlet):
Unit Model LSW-
|
30SL |
40SL |
50SL |
80SL |
100SL |
120SL |
160SL |
200SL |
||
nominal refrigerating capacity |
KW |
98.4 |
134.1 |
176 |
319.2 |
378.1 |
495.3 |
643.9 |
823.6 |
|
Kcal/h |
84600 |
115300 |
151300 |
274500 |
325100 |
425900 |
553700 |
708200 |
||
Refrigerant |
R22 |
|||||||||
Refrigerant quantity |
kg |
20 |
25 |
40 |
50 |
65 |
75 |
100 |
130 |
|
Power supply voltage |
3/N/PE AC380/220V 50Hz |
|||||||||
Control mode |
microcomputer programmable control |
|||||||||
Protection function |
Refrigeration high and low pressure protection, water system fault protection, antifreeze protection, compressor overheating overload protection, etc. |
|||||||||
Energy control section |
% |
0/25/50/75/100 |
0/25/50/75/100 |
|||||||
Number of compressors |
Taiwan |
1 |
1 |
|||||||
Compressor power |
KW |
23.9 |
31.5 |
46.9 |
68 |
81.7 |
105.5 |
134 |
171.3 |
|
Cooling water |
Inlet and outlet water temperature |
℃ |
32/37 |
|||||||
Flow |
T/h |
22 |
30 |
40 |
70 |
83 |
108 |
140 |
179 |
|
Water resistance |
MPa |
≤ 0.07 |
||||||||
Pipe diameter |
Flange |
DN65 |
DN80 DN100 |
DN100 DN125 |
DN125 DN150 |
|||||
chilled water |
Inlet and outlet water temperature |
℃ |
12/7 |
|||||||
Flow |
T/h |
18 |
24 |
32 |
57 |
68 |
94 |
116 |
148 |
|
Water resistance |
MPa |
≤ 0.07 |
||||||||
Pipe diameter |
Flange |
DN65 |
DN80 |
DN100 |
DN125 DN125 DN150 |
|||||
Dimensions |
Long |
mm |
2400 |
2600 |
2800 |
3000 |
3200 |
3200 |
3300 |
3500 |
Wide |
mm |
900 |
900 |
900 |
1100 |
1100 |
1100 |
1100 |
1100 |
|
High |
mm |
1400 |
1400 |
1500 |
1800 |
1800 |
2000 |
2100 |
2100 |
|
Unit weight |
Kg |
900 |
1100 |
1300 |
1800 |
2400 |
2650 |
3300 |
3500 |
Remarks:
1
Refrigeration condition: inlet temperature of frozen water12℃, outlet temperature of frozen water7℃, cooling water inlet temperature30℃, water outlet temperature of cooling water35℃;
2Safety working range of unit: chilled water temperature5~30℃;
3Power Control:3 ¢/380V/50HZ,Allowable voltage fluctuation±10%Allowable phase-to-phase voltage difference±2%;
4The above dataR22The unit performance parameters for the refrigerant, if required.R134a,R407COther working quality please call consultation;
5Due to technical improvement, the external dimensions are likely to change. The external dimensions are for reference only. Please ask for the installation dimension drawing at any time.
Water-cooled screw chiller parameter table (-10 ℃ water outlet):
Unit Model LSW-
|
30SL |
40SL |
50SL |
80SL |
100SL |
120SL |
160SL |
200SL |
||
nominal refrigerating capacity |
KW |
45.4 |
61.9 |
81.2 |
147.3 |
174.5 |
228.6 |
297.2 |
380.1 |
|
Kcal/h |
39000 |
53200 |
69800 |
126700 |
150000 |
196600 |
255500 |
326800 |
||
Refrigerant |
R22 |
|||||||||
Refrigerant quantity |
kg |
20 |
25 |
40 |
50 |
65 |
75 |
100 |
130 |
|
Power supply voltage |
3/N/PE AC380/220V 50Hz |
|||||||||
Control mode |
microcomputer programmable control |
|||||||||
Protection function |
Refrigeration high and low pressure protection, water system fault protection, antifreeze protection, compressor overheating overload protection, etc. |
|||||||||
Energy control section |
% |
0/25/50/75/100 |
0/25/50/75/100 |
|||||||
Number of compressors |
Taiwan |
1 |
1 |
|||||||
Compressor power |
KW |
20.1 |
26.5 |
33.2 |
57.2 |
68.7 |
88.7 |
112.8 |
144.1 |
|
Cooling water |
Inlet and outlet water temperature |
℃ |
32/37 |
|||||||
Flow |
T/h |
12 |
17 |
22 |
39 |
46 |
60 |
77 |
99 |
|
Water resistance |
MPa |
≤ 0.07 |
||||||||
Pipe diameter |
Flange |
DN65 |
DN80 DN100 |
DN100 DN125 |
DN125 DN150 |
|||||
chilled water |
Inlet and outlet water temperature |
℃ |
12/7 |
|||||||
Flow |
T/h |
10 |
13 |
17 |
32 |
38 |
49 |
64 |
82 |
|
Water resistance |
MPa |
≤ 0.07 |
||||||||
Pipe diameter |
Flange |
DN65 |
DN80 |
DN100 |
DN125 DN125 DN150 |
|||||
Dimensions |
Long |
mm |
2400 |
2600 |
2800 |
3000 |
3200 |
3200 |
3300 |
3500 |
Wide |
mm |
900 |
900 |
900 |
1100 |
1100 |
1100 |
1100 |
1100 |
|
High |
mm |
1400 |
1400 |
1500 |
1800 |
1800 |
2000 |
2100 |
2100 |
|
Unit weight |
Kg |
900 |
1100 |
1300 |
1800 |
2400 |
2650 |
3300 |
3500 |
Remarks:
1
Refrigeration condition: inlet temperature of frozen water-5℃, outlet temperature of frozen water-10℃, cooling water inlet temperature30℃, water outlet temperature of cooling water35℃;
2Safety working range of unit: chilled water temperature -15~10℃;
3Power Control:3 ¢/380V/50HZ,Allowable voltage fluctuation±10%Allowable phase-to-phase voltage difference±2%;
4The above dataR22The unit performance parameters for the refrigerant, if required.R134a,R407COther working quality please call consultation;
5Due to technical improvement, the external dimensions are likely to change. The external dimensions are for reference only. Please ask for the installation dimension drawing at any time.
Related Products